114
IRUS TotalDownloads
Altmetric
Benefits of Operating a Four Terminal HVDC Network with a Normally Open Point
File | Description | Size | Format | |
---|---|---|---|---|
Benefits of Operating a Four Terminal HVDC Network with a Normally Open Point.pdf | Accepted version | 740.41 kB | Adobe PDF | View/Open |
Title: | Benefits of Operating a Four Terminal HVDC Network with a Normally Open Point |
Authors: | Sheridan, CE Merlin, MMC Green, TC |
Item Type: | Conference Paper |
Abstract: | It is likely that any HVDC grids will evolve over time and will likely be multi-vendor and use several different technologies. This paper studies a four terminal network where the interconnecting link is operated as a normally open point. This allows the network to be reconfigured in the event of DC side fault, without the need for DC circuit breakers. The network uses the popular Modular Multi-level converter at one terminal and a fault tolerant converter at the other terminal. A simple cost benefit shows the economic advantage of the interconnecting link. The operation of this network is then verified through simulation for a normal operating scenario and a DC fault scenario. |
Issue Date: | 21-Oct-2015 |
Date of Acceptance: | 21-Oct-2015 |
URI: | http://hdl.handle.net/10044/1/27256 |
Copyright Statement: | © 2015 the Authors |
Conference Name: | International High Voltage Direct Current Conference 2015 |
Keywords: | HVDC Energy conversion Fault blocking converters Modular multilevel converter Multi-terminal DC |
Start Date: | 2015-10-18 |
Finish Date: | 2015-10-22 |
Conference Place: | Seoul, South Korea |
Appears in Collections: | Electrical and Electronic Engineering Faculty of Engineering |