Fire experiment inside a very large and open-plan compartment: x-ONE
File(s)
OA Location
Author(s)
Rackauskaite, Egle
Bonner, Matthew
Restuccia, Francesco
Anez, Nieves Fernandez
Christensen, Eirik G
Type
Journal Article
Abstract
The traditional design fires commonly considered in structural fire engineering, like the standard fire and Eurocode parametric fires, were developed several decades ago based on experimental compartments smaller than 100 m2 in floor area. These experiments led to the inherent assumption of flashover in design fires and that the temperatures and burning conditions are uniform in the whole of the compartment, regardless of its size. However, modern office buildings often have much larger open-plan floor areas (e.g. the Shard in London has a floor area of 1600 m2) where non-uniform fire conditions are likely to occur. This paper presents observations from a large-scale fire experiment x-ONE conducted inside a concrete farm building in Poland. The objective of x-ONE was to capture experimentally a natural fire inside a large and open plan compartment. With an open-plan floor area of 380 m2, x-ONE is the largest compartment fire experiment carried out to date. The fire was ignited at one end of the compartment and allowed to spread across a continuous wood crib (fuel load ~ 370 MJ/m2). A travelling fire with clear leading and trailing edges was observed spreading along 29 m of the compartment length. The flame spread rate was not constant but accelerated with time from 3 mm/s to 167 mm/s resulting in a gradually changing fire size. The fire travelled across the compartment and burned out at the far end 25 min after ignition. Flashover was not observed. The thermocouples and cameras installed along the fire path show clear near-field and far-field regions, indicating highly non-uniform spatial temperatures and burning within the compartment. The fire dynamics observed during this experiment are completely different to the fire dynamics reported in small scale compartments in previous literature and to the assumptions made in traditional design fires for structural design. This highlights the need for further research and experiments in large compartments to understand the fire dynamics and continue improving the safe design of modern buildings.
Date Issued
2021-09-30
Date Acceptance
2021-07-20
Citation
Fire Technology, 2021, 58, pp.905-939
ISSN
0015-2684
Publisher
Springer
Start Page
905
End Page
939
Journal / Book Title
Fire Technology
Volume
58
Copyright Statement
© 2021 The Author(s). Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article's Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article's Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativecommons.org/licenses/by/4.0/.
License URL
Identifier
http://gateway.webofknowledge.com/gateway/Gateway.cgi?GWVersion=2&SrcApp=PARTNER_APP&SrcAuth=LinksAMR&KeyUT=WOS:000702217000001&DestLinkType=FullRecord&DestApp=ALL_WOS&UsrCustomerID=1ba7043ffcc86c417c072aa74d649202
Subjects
Science & Technology
Technology
Engineering, Multidisciplinary
Materials Science, Multidisciplinary
Engineering
Materials Science
Flame spread
Travelling
Compartment
Flashover
Design fire
TRAVELING FIRES
CONCRETE
SAFETY
TESTS
Publication Status
Published
Date Publish Online
2021-09-30