Fault response of inverter-based distributed generation
Author(s)
Plet, Cornelis Arie
Type
Thesis
Abstract
The work presented in this thesis focuses on developing and experimentally verifying accurate analytical
equivalent models of inverters during short-circuit conditions for use in numerical fault studies. In addition,
a concept design for a variable speed generator that does not contribute to the local fault level is presented
and verified by simulation and experiment.
The flexibility of control offered by the application of power electronics in distribution networks is
paramount in the transition to a decentralised power system but still faces significant technical challenges
to widespread integration into the incumbent utility grid. Power electronic interfaces have historically only
been used in rare cases and their effect on the network has hitherto often been ignored. The uptake of
energy sources such as photovoltaics, variable speed wind, fuel cells, microturbines has caused a sufficient
increase in grid connection requests for inverter interfaced generators, that before long their fault behaviour
can no longer be neglected.
The fault response of an inverter is dictated by its control strategy, its current limiting strategy and the
reference frame in which they have been implemented. Current limiting typically breaks an inverter’s outer
control loop and effectively turns it into a current source. Depending on the exact method of current limiting,
linear analytical equivalent models have been developed whose source and impedance values can be
expressed as a function of the inverters hardware parameters and controller gains evaluated at the fundamental
frequency. The resulting models are compatible with conventional network analysis techniques and
have been verified by comparing the results of such an analysis with experimental results. Fault models
have been developed for stand-alone and grid-connected inverters.
In congested networks the connection of an additional generator can cause the substation circuit breaker
ratings to be exceeded. A full inverter interface can be controlled not to contribute to the fault current but
is still prohibitively expensive at higher power levels. An alternative generator based on a doubly-fed
induction generator is proposed and experimentally tested. By inserting a tap in the rotor winding, the
voltage-per-turn can temporarily be increased to retain control of the quickly rising fault current without
having to upgrade the machine-side inverter’s ratings.
A fast thyristor-based tap changer inverter is proposed and experimentally verified that performs the
pulse width modulation and diverts the modulated waveform to the desired tap on the rotor winding. The
tap changer can be commutated in such a way as to achieve the fastest possible rate of current transfer during
a tap change whilst avoiding voltage spikes by allowing any energy stored in the rotor leakage inductance
to return to the DC-link.
The developed fault models and zero fault current generator are a step towards familiarising utility engineers
with power electronics and how they affect the operation of the distribution network. The availability
of standardised models avoids the need for expensive and time-consuming time domain simulation based
fault studies for inverter connection requests. The work presented in this thesis may act as a base for the
development of standardised representations of power electronics in power networks.
equivalent models of inverters during short-circuit conditions for use in numerical fault studies. In addition,
a concept design for a variable speed generator that does not contribute to the local fault level is presented
and verified by simulation and experiment.
The flexibility of control offered by the application of power electronics in distribution networks is
paramount in the transition to a decentralised power system but still faces significant technical challenges
to widespread integration into the incumbent utility grid. Power electronic interfaces have historically only
been used in rare cases and their effect on the network has hitherto often been ignored. The uptake of
energy sources such as photovoltaics, variable speed wind, fuel cells, microturbines has caused a sufficient
increase in grid connection requests for inverter interfaced generators, that before long their fault behaviour
can no longer be neglected.
The fault response of an inverter is dictated by its control strategy, its current limiting strategy and the
reference frame in which they have been implemented. Current limiting typically breaks an inverter’s outer
control loop and effectively turns it into a current source. Depending on the exact method of current limiting,
linear analytical equivalent models have been developed whose source and impedance values can be
expressed as a function of the inverters hardware parameters and controller gains evaluated at the fundamental
frequency. The resulting models are compatible with conventional network analysis techniques and
have been verified by comparing the results of such an analysis with experimental results. Fault models
have been developed for stand-alone and grid-connected inverters.
In congested networks the connection of an additional generator can cause the substation circuit breaker
ratings to be exceeded. A full inverter interface can be controlled not to contribute to the fault current but
is still prohibitively expensive at higher power levels. An alternative generator based on a doubly-fed
induction generator is proposed and experimentally tested. By inserting a tap in the rotor winding, the
voltage-per-turn can temporarily be increased to retain control of the quickly rising fault current without
having to upgrade the machine-side inverter’s ratings.
A fast thyristor-based tap changer inverter is proposed and experimentally verified that performs the
pulse width modulation and diverts the modulated waveform to the desired tap on the rotor winding. The
tap changer can be commutated in such a way as to achieve the fastest possible rate of current transfer during
a tap change whilst avoiding voltage spikes by allowing any energy stored in the rotor leakage inductance
to return to the DC-link.
The developed fault models and zero fault current generator are a step towards familiarising utility engineers
with power electronics and how they affect the operation of the distribution network. The availability
of standardised models avoids the need for expensive and time-consuming time domain simulation based
fault studies for inverter connection requests. The work presented in this thesis may act as a base for the
development of standardised representations of power electronics in power networks.
Date Issued
2011
Date Awarded
2012-03
Copyright Statement
Attribution NoDerivatives 4.0 International Licence (CC BY-ND)
Advisor
Green, Tim
Publisher Department
Electrical and Electronic Engineering
Publisher Institution
Imperial College London
Qualification Level
Doctoral
Qualification Name
Doctor of Philosophy (PhD)